Carat Digitron M 04 is an alternating current four tariff static electricity meter for active energy – single phase. The model has an inbuilt 100 A relay for switching on and off the power supply of the consumer, 20 mA current loop interface; indication for opening of the cover.
Technology |
Modern SIGMA DELTA technology for analogue-to-digital transformation, realized through specialized processor of the leading ANALOG DEVICES Company, micro processing control and SMD assembly |
Application |
It is designed for precise measurement of single-phase active energy in offices, residential, commercial outlets and others |
Wiring diagram |
Single phase, direct, common null, 2 wires, use of current sensor shunt |
Assembly diagram |
Three-point attachment as per IEC 61039 or to a standard bar DIN EN 50022 and DIN 43880 |
Complies with EN 61036 : 1996 + А1 : 2000 |
||
Rated voltage Un |
220V |
|
Range of voltage |
(0,8 – 1,15) Un V |
|
Rated frequency |
50 Hz ± 5% |
|
Rated current lb |
10А |
|
Maximum current lmax |
60A |
|
Starting current |
0,004 lb A |
|
Power consumption |
≤ 1,5W |
|
Accuracy class |
1 |
|
Meter constant |
1600 imp/KWh |
|
Display |
8-digit LCD display with additional data fields and cyclic reading from the tariff register |
|
Registration and indication of energy in reverse direction |
||
Access and parameterization passwords |
||
Impossibility for zeroing the energy registers by the customer |
||
Resistance to high frequency electromagnetic fields, static electricity discharges and RF influence |
||
Communication |
20 mA current loop interface – EN 62056-21 |
|
Software for parameterization reading and diagnostics in Windows environment |
||
Built-in clock and calendar |
0,5 s/24h |
|
Operating temperature range |
From -25oC to 55oC |
|
Storing temperature range |
From -40oC to 70oC |
|
Dust and water protection |
IP 54 |
|
Protection degree |
Class II |
|
Dimensions |
166/100/52,5 mm |
|
Weight |
0,450kg |